General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 14 , |
Rated voltage | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Power dissipation | 1.8 W |
Power consumption | max. 2.7 W |
Input |
Connection side | field side |
Connection | terminals 1 , 3-; 4 , 6- |
Input signal | 0/4 ... 20 mA |
Available voltage | ≥ 16 V at 20 mA, terminals 1 , 3 |
Output |
Connection side | control side |
Connection | terminals 7-, 8 ; 10-, 11 |
Load | 0 ... 550 Ω at 20 mA |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Ripple | max. 50 ?A rms |
Transfer characteristics |
Deviation | at 20 ?C (68 ?F), 0/4 ... 20 mA ≤ 10 ?A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Frequency range | field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB) |
Settling time | 200 ?s |
Rise time/fall time | 20 ?s |
Indicators/settings |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 ?C (-4 ... 140 ?F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |